For sales and support visit:
hubbellpowersystems.com/contact/
PVI-LP Intermediate
Class Arresters
[3kV - 72kV Rated]

PVI-LP (Low Profile Housing)


PVI-LP Terminals:

Standard line and ground terminal and standard domestic packaging: use code3001 (Example: 3008XX3001, Figure 1) Four hole NEMA line terminal, standard ground terminal and domestic packaging: use code 3002 (Example: 3008XX3002, Figure 2)) Other options: For underhung mounting: use catalog number 3028XX3001 or 3028XX3002.

Base Mounting Information:

The end casting is furnished with three slots suitable for use on either 8.75" or 10" diameter bolt circle. Mounting hardware is not furnished with the arrester.

Bolt Size (Inches) Attachment Lug
Thickness (Inches) Slot Width (Inches)
0.5 0.75 0.56

Protective Characteristics

Standard Arrester Catalog Number Duty Cycle Rating kV rms Maximum Continuous Operating Voltage kV rms Maximum 0.5?s Discharge Voltage kV (1) Maximum Switching Surge Protective Level kV (2) Maximum Discharge Voltage Using an 8/20 Current Wave-kV
1.5 kA 3 kA 5 kA 10 kA 20 kA 40 kA
300803 3 2.55 8.6 6.4 6.8 7.2 7.5 8.1 9.0 10.1
300805 6 5.1 17.1 12.7 13.6 14.4 15.0 16.2 17.9 20.2
300808 9 7.65 25.8 19.1 20.5 21.6 22.6 24.4 27.0 30.4
300809 10 8.4 28.4 21.1 22.6 23.8 24.9 26.9 29.8 33.5
300610 12 10.2 34.1 25.3 27.1 28.6 29.9 32.3 35.8 40.3
300813 15 12.7 42.9 31.8 34.1 36.0 37.6 40.6 44.9 50.6
300815 18 15.3 51.6 38.3 40.9 43.2 45.2 48.8 54.0 60.9
300817 21 17.0 56.9 42.2 45.1 47.7 49.9 53.8 59.6 67.1
300620 24 19.5 68.3 50.6 54.2 57.2 59.9 64.6 71.5 80.6
300822 27 22.0 77.4 57.4 61.4 64.9 67.9 73.2 81.0 91.3
300824 30 24.4 85.3 63.3 67.7 71.5 74.8 80.7 89.3 101.0
300629 36 29.0 102.0 76.0 81.3 85.9 89.8 96.9 107.0 121.0
300831 39 31.5 108.4 80.4 86.1 90.9 95.1 102.6 113.6 127.9
300636 45 36.5 125.1 92.8 99.3 104.9 109.8 118.4 131.1 147.6
300639 48 39.0 136.6 101.3 108.4 114.5 119.8 129.2 143.0 161.1
300642 54 42.0 147.9 109.7 117.4 125.0 129.7 139.9 154.9 174.5
300648 60 48.0 165.0 122.4 131.0 138.3 144.7 156.1 172.8 195.0
300657 72 57.0 199.0 147.7 158.1 166.9 174.6 188.4 209.0 235.0

Dimensions and Mounting

Type Catalog Number MCOV "X" Dimension (inches) Leakage Distance (inches) Minimum Mounting Spacing on Center (inches) Net Weight (pounds)
Ph-Ph Ph-Grd
PVI-LP 300803 2.55 6.8 15.4 4.4 3.3 6.2
PVI-LP 300805 5.1 6.8 15.4 4.6 3.2 6.2
PVI-LP 300808 7.65 6.8 15.4 4.7 3.3 6.2
PVI-LP 300809 8.4 6.8 15.4 4.9 3.5 6.2
PVI-LP 300610 10.2 6.8 15.4 4.9 3.5 6.2
PVI-LP 300813 12.7 12.2 30.8 6.2 4.8 10.0
PVI-LP 300815 15.3 12.2 30.8 6.6 5.2 10.0
PVI-LP 300817 17.0 12.2 30.8 7.6 6.2 10.0
PVI-LP 300620 19.5 12.2 30.8 7.6 6.2 10.0
PVI-LP 300822 22.0 17.6 46.2 9.6 8.2 13.5
PVI-LP 300824 24.4 17.6 46.2 9.8 8.4 13.5
PVI-LP 300629 29.0 17.6 46.2 9.8 8.4 13.5
PVI-LP 300831 31.5 23.0 61.6 12.8 11.4 17.0
PVI-LP 300636 36.5 23.0 61.6 12.8 11.4 17.0
PVI-LP 300639 39.0 23.0 61.6 12.8 11.4 17.0
PVI-LP 300642 42.0 28.4 77.0 15.8 14.4 19.6
PVI-LP 300648 48.0 28.4 77.0 15.8 14.4 19.6
PVI-LP 300657 57.0 33.8 92.4 19.8 18.4 23.1
Pressure Relief
Capability-Symmetrical rms kA:
16.1 (Minimum required by ANSI C62.11)
Energy Capability: 6.0 kJ/kV MCOV, based on one minute thermal recovery test
Cantilever Strength: Maximum working cantilever moment with the tripod base - 2000 inch pounds
Rated ultimate cantilever moment with the tripod base - 4000 inch pounds
Hubbell Power Systems All contents Copyright© 2001 - Hubbell Incorporated. All rights reserved. Because Hubbell has a policy of continuous product improvement, we reserve the right to change design specifications without notice.