Standard Arrester Catalog Number Duty Cycle Rating kV rms Maximum Continuous Operating Voltage (MCOV) kV rms Maximum 0.5 µs Discharge Voltage kV (1) Maximum Switching Surge Protective Level kV (2) TOV Capability (3) Maximum Discharge Voltage using an 8/20 Current Wave-kV
1 sec kV rms 10 sec kV rms 1.5kA 3kA 5kA 10kA 20kA 40kA
EVP000300 3 2.55 10.5 6.0 3.62 3.47 6.4 6.7 7.1 7.6 8.2 9.3
EVP000500 6 5.1 18.6 12.0 7.25 6.94 12.8 13.5 14.1 15.2 16.4 18.7
EVP000800 9 7.65 27.0 18.0 10.9 10.4 19.2 20.2 21.2 22.7 24.6 28.0
EVP000900 10 8.4 29.4 19.8 11.9 11.4 21.1 22.2 23.3 25.0 27.0 30.8
EVP001000 12 10.2 35.1 24.0 14.5 13.9 25.6 26.9 28.2 30.3 32.8 37.4
EVP001300 15 12.7 43.4 29.9 18.0 17.3 31.9 33.5 35.2 37.7 40.8 46.5
EVP001500 18 15.3 51.6 36.1 21.7 20.8 38.5 40.4 42.4 45.5 49.1 56.1
EVP001700 21 17 57.8 40.1 24.2 23.1 42.7 44.9 47.1 50.5 54.6 62.3
EVP001900 24 19.5 65.7 45.9 27.7 26.5 49.0 51.5 54.0 57.9 62.6 71.4
EVP002200 27 22 73.6 51.8 31.3 29.9 55.3 58.1 60.9 65.4 70.7 80.6
EVP002400 30 24.4 81.2 57.5 34.7 33.2 61.3 64.5 67.6 72.5 78.4 89.4
EVP002900 36 29 97.0 68.6 41.4 39.6 73.2 76.9 80.7 86.5 93.6 107
EVP003100 39 31.5 105 74.4 44.8 42.9 79.3 83.4 87.4 93.8 101 116
EVP003600 45 36.5 121 86.0 51.9 49.6 91.8 96.4 101 108 117 134
EVP003900 48 39 129 91.9 55.4 53.0 98.0 103 108 116 125 143
EVP004200 54 42 145 104 62.5 59.8 111 116 122 131 141 161
EVP004800 60 48 160 114 69.0 66.0 122 128 134 144 156 178
EVP005700 72 57 192 137 82.8 79.3 147 154 161 173 187 214
EVP007000 90 70 242 172 104 99.3 184 193 202 217 234 267
EVP007400 90 74 245 174 105 101 186 195 205 220 238 271
EVP007600 96 76 257 184 111 106 196 206 216 232 251 286
EVP008400 108 84 289 207 125 120 221 232 244 261 283 322
EVP008800 108 88 289 207 125 120 221 232 244 261 283 322
EVP009800 120 98 322 241 139 133 246 259 271 291 315 359
EVP010600 132 106 350 262 152 145 268 282 296 317 343 391
EVP011500 144 115 382 286 166 159 293 308 323 346 375 427
EVP013100 168 131 447 334 194 185 342 360 377 405 438 499
EVP014000 172 140 462 344 199 191 352 370 388 416 450 513
EVP014400 180 144 480 357 207 198 366 385 403 433 468 534
EVP015200 192 152 510 381 221 211 391 411 430 462 499 569
EVP018000 228 180 605 453 262 251 464 487 511 548 593 676

Dimensions and Mounting

Standard Arrester Catalog Number Duty Cycle Rating kV rms Maximum Continuous Operating Voltage (MCOV) kV rms Height Dimension (Inches) Leakage Distance (Inches) Recommended Minimum Clearance (Inches) Net Weight (Pounds)
Ph - Ph Ph - Grd
EVP000300 3 2.55 9.9 19.6 9 4.5 13
EVP000500 6 5.1 9.9 19.6 9 4.5 13
EVP000800 9 7.65 11.7 30.1 9 4.5 15
EVP000900 10 8.4 11.7 30.1 9 4.5 15
EVP001000 12 10.2 11.7 30.1 9 4.6 15
EVP001300 15 12.7 13.5 35.4 9.7 5.4 17
EVP001500 18 15.3 13.5 35.4 10.6 6.1 17
EVP001700 21 17 17.2 40.5 11.2 6.7 22
EVP001900 24 19.5 17.2 40.5 12.1 7.4 22
EVP002200 27 22 17.2 40.5 12.9 8.2 22
EVP002400 30 24.4 17.2 40.5 13.8 8.9 22
EVP002900 36 29 20.9 50.9 15.4 10.3 27
EVP003100 39 31.5 20.9 50.9 16.2 11.1 27
EVP003600 45 36.5 24.5 61.5 17.9 12.6 31
EVP003900 48 39 24.5 61.5 18.8 13.3 31
EVP004200 54 42 24.5 61.5 20.5 14.9 31
EVP004800 60 48 28.2 71.9 22.1 16.2 36
EVP005700 72 57 31.9 82.4 25.4 19.2 41
EVP007000 90 70 46.3 123 30.5 23.7 59
EVP007400 90 74 46.3 123 30.8 24 59
EVP007600 96 76 46.3 123 32.2 25.2 59
EVP008400 108 84 46.3 123 35.6 28.2 59
EVP008800 108 88 46.3 123 35.6 28.2 59
EVP009800 120 98 53.7 143.9 48.6 36 73
EVP010600 132 106 53.7 143.9 51.6 38.7 73
EVP011500 144 115 61 164.8 55 41.7 82
EVP013100 168 131 72.5 184.5 61.7 47.7 97
EVP014000 172 140 83.5 215.8 74.4 60.5 120
EVP014400 180 144 83.5 215.8 76.3 62.4 120
EVP015200 192 152 83.5 215.8 79.7 65.8 120
EVP018000 228 180 94.5 247.2 89.7 75.7 133

 

Grading Ring Diameters

Arrester MCOV Drop (A) (inches) Diameter (B) (inches)
98 - 131 9.0 16.5
140 - 180 14.5 27.9

 