VLA Porcelain Station [3kV - 24kV Rated]

Protective Characteristics

Type Standard Arrester Catalog Number Duty Cycle Rating kV rms Arrester MCOVkV rms Maximum 0.5?s Discharge Voltage kV (1) Maximum Switching Surge Protective Level At Classifying Current Levels kV (2) Maximum Discharge Voltage Using an 8/20 Current Wave-kV
1.5kA 3kA 5kA 10kA 20kA 40kA
VLA 217003 3 2.55 9.1 6.3 6.9 7.2 7.5 8 9 10.3
VLA 217005 6 5.1 17.9 12.4 13.6 14.2 14.8 15.8 17.7 20.3
VLA 217008 9 7.65 26.6 18.4 20.2 21.1 22 23.5 26.4 30.2
VLA 217009 10 8.4 29.3 20.3 22.2 23.3 24.2 25.9 29.1 33.3
VLA 218510 12 10.2 35.5 24.6 26.9 28.2 29.4 31.4 35.2 40.4
VLA 217013 15 12.7 44.2 30.6 33.5 35.1 36.6 39.1 43.9 50.3
VLA 217015 18 15.3 53.3 36.8 40.4 42.3 44.1 47.1 52.8 60.6
VLA 218517 21 17.0 59.1 40.9 44.8 46.9 48.9 52.3 58.7 67.2
VLA 218519 24 19.5 67.8 46.9 51.4 53.8 56.1 60 67.3 77.1

Dimensions and Mounting

See the Dimensions and Mounting Table for more detailed information.

Type Standard Arrester Catalog Number Duty Cycle Rating kV rms Maximum Continuous Operating Voltage kV rms Drawing Number "X" Dimension (Inches) Minimum Leakage Distance (Inches) Minimum Mounting Spacing on center&dagger Net Weight (Pounds)
Phase to Phase (in-line (Inches) Phase to Ground (Inches)
VLA 217003 3 2.55 1 12 11.1 11 5.5 35
VLA 217005 6 5.1 1 12 11.1 11 5.5 40
VLA 217008 9 7.65 1 12 11.1 11 5.5 40
VLA 217009 10 8.4 1 12 11.1 11 5.5 40
VLA 218510 12 10.2 1 12 11.1 11 6.5 42
VLA 217013 15 12.7 1 16.25 20 11 7.5 50
VLA 217015 18 15.3 1 16.25 20 11 9 50
VLA 218517 21 17.0 1 16.25 20 11 9 51
VLA 218519 24 19.5 1 16.25 20 11 9 52