Home › Products › Cable Accessories › 600A Deadbreak (15/25kV) › Junctions › Tap Master™ (Epoxy)
| Description | Ratings |
|---|---|
| Operating Voltage Maximum line-to-ground |
15.2kV |
| BIL Impulse withstand 1.2 x 50 μsec |
125kV |
| Withstand Voltage AC One Minute DC Fifteen Minute |
40kV 78kV |
| Corona Extinction Level @ 3pC Sensitivity |
19kV |
| Continuous Current | 600 amp |
| 24 Hour Overload | 1,000 A rms |
| Symmetrical Momentary Current |
25 kA rms sym. for 0.17 sec 10 kA rms sym. for 3.0 sec |
The 25kV TapMaster™ junction offers a complete change in design approach, addressing the issues of space savings in vaults and enclosures, mounting flexibility and the flexibility of locating parking stands to accept accessory products required to operate and maintain a distribution system.
|
|
All contents Copyright© 2001 -
Hubbell Incorporated. All rights reserved. Because Hubbell has a policy of
continuous product improvement, we reserve the right to change design specifications
without notice.
Terms of Use | Contact Us | Site Map |