For sales and support visit:
hubbellpowersystems.com/contact/

Description

RATINGS
Max. continuous voltage: 8.3 kV phase-to-ground
14.4 kV phase-to-phase
Continuous current: 200 amp rms
SHORT-TIME CURRENT RATINGS
0.17-second duration 10,000 amp rms symmetrical
3.00-second duration 3,500 amps rms symmetrical
INSULATION WITHSTAND VOLTAGES
Basic Impulse Level
(1.2 x 50 microsec. wave)
95 kV crest
60 Hertz (one minute) 34 kV rms
Dc (15 minutes) 53 kV
Corona extinction voltage
(3 picocoulombs)
11 kV rms
SWITCHING
1-phase and 3-phase circuits 8.3 kV phase-to-ground, 14.4 kV maximum across the open contacts. 10 loadmake/loadbreak operations at 200 amps with 90% parallel and 10% series resistance - reactance load at 0.8 power factor.
FAULT CLOSURE
One fault-close operation at 8.3 kV phase-to-ground, or 14.4 kVphase-to-phase; 10,000 amps rms symmetrical, 10 cycles,(0.17 seconds).
PRODUCTION TESTS
100% factory test for partial discharge and either AC Hi-Pot (34kV for 60 seconds) or impulse (BIL) (95kV 1.2 x 50μ sec.).

GENERAL INFORMATION

Hubbell 8.3/14.4 kV underground connectors provide utilities with products having high reliability and low maintenance expense.

These connectors provide:

  • 10,000-amp fault-closing capability
  • Piston-operated fault-close action
  • Standard elbow and bushing insert loadbreak principle
  • 1/8" thick Molded shields
  • Peroxide-cured EPDM compounds
  • Full compliance with IEEE Standard 386

Hubbell separable connector bushing inserts and elbows are designed for use with single-conductor, concentric neutral power cable having extruded insulation shielding. With shield adapter products, the elbow can be used with cables having a metallic tape shield, wire shield, or lead sheath with tape or extruded insulation shielding.

All insulating and conducting rubber components are made of a special formulation of an EPDM elastomer using a peroxide curing process. The material and curing process provides superior elastomer stress relaxation characteristics under high ambient temperatures and contributes to reliable, long-time operation in either aboveground or subsurface installations.

Elbow connector/bushing insert combinations are suitable for energized loadmake/loadbreak operations by a qualified lineman using an 8’ shotgun-type hot stick.

All elbow/bushing insert combinations are designed for use with subsurface (submersible to 6 feet of water) or pad-mounted installations.

Where to Use

Hubbell 15 kV loadbreak products are designed for operation on and connection to 15 kV class, 95 kV BIL systems where the voltage ratings listed on this page are not exceeded.

Hubbell Power Systems All contents Copyright© 2001 - Hubbell Incorporated. All rights reserved. Because Hubbell has a policy of continuous product improvement, we reserve the right to change design specifications without notice.
Terms of Use | Contact Us | Site Map
Cable Accessories