Home › Products › Cable Accessories › 200A Loadbreak › 15kV › Elbow
Hubbell Loadbreak Elbows provide utilities with products having high reliability and low maintenance expense.
The elbow, when mated with a loadbreak bushing product meeting the requirment of IEEE Standard 386, is suitable for energized loadmake / loadbreak operations by a qualified lineman using a shotgun-type hot stick.
Cable Dimension Reference
(1) If insulation shield is not extruded, an adapter must be used to accommodate elbow.
Step 1: Determine the cable's insulation diameter either by measuring it (Do not measure over the insulation shield) or from the cable manufacturer's catalog. Select an elbow size from table "w" so that the insulation falls within the elbow's range.
Step 2: Select a connector code from table "x" that identifies the conductor size and stranding. Standard compression lug is a long bi-metal connector.
Step 3: If the elbow is to be supplied with a capacitance test point add a "T" to the end of the part number.
| Table W | ||
|---|---|---|
| Insulation Min/Max | ||
| Elbow Size | Inches | mm |
| 3 | 0.495" - 0.730" | 12,5 - 18,5 |
| 4 | 0.635" - 0.905" | 16,1 - 23,0 |
| 5 | 0.760" - 1.135" | 19,3 - 28,8 |
| Table X (AL or CU Conductor) |
||
|---|---|---|
| Connector Code | Stranded or Compressed | Compact or Solid |
| 1 | #6 | #4 |
| 2 | #3 or #4 | #2 or #3 |
| 3 | #2 | #1 |
| 4 | #1 | 1/0 |
| 5 | 1/0 | 2/0 |
| 6 | 2/0 | 3/0 |
| 7 | 3/0 | 4/0 |
| 8 | 4/0 | 250 |
Example, the part number for a 15kV loadbreak elbow with test point for 1/0 stranded, 175mil insulation with an 0D over insulation of 0.785" would be: 215LE45T.
To specify this same elbow kit but with a ProbeLok® connector, add a "P" after the connector code, i.e. 215LE45PT.
To order a loadbreak elbow with an integral seal add a "J" after the "LE" in the part number. For an example: 215LEJ45T.
To order an elbow kit without a compression connector use part number: 215LE40T.
If the kit is to be supplied with a separate, cold-shrink seal kit for use on concentric neutral cables, add a "J" to the end of the part number. For example: 215LE45TJ.
If a cold-shrink, shield adapter is to be included in the kit, add an "S" to the end of the part number: 215LE45TS.
To order a replacement probe, use part number 215LBP.
To order a replacement compression connector, use part number 200LUGBx.
|
|