Home › Products › Cable Accessories › 200A Loadbreak › 25kV › Description
| RATINGS | |
|---|---|
| Max. continuous voltage: | 15.2 kV phase-to-ground 26.3 kV phase-to-phase |
| Continuous current: | 200 amp rms |
| SHORT-TIME CURRENT RATINGS | |
| 0.17-second duration | 10,000 amp rms symmetrical |
| 3.00 second duration | 3,500 amps rms symmetrical |
| INSULATION WITHSTAND VOLTAGES | |
| Basic Impulse Level (1.2 x 50 microsec. wave) |
125 kV crest |
| 60 Hertz (one minute) | 40 kV rms |
| Dc (15 minutes) | 78 kV |
| Corona extinction voltage (3 picocoulombs) |
19 kV rms |
| SWITCHING | |
| 1-phase and 3-phase circuits 15.2 kV phase-to-ground, 26.3 kV maximum across the open contacts. | 10 loadmake/loadbreak operations at 200 amps with 90% parallel and 10% series resistance - reactance load at 0.8 power factor. |
| FAULT CLOSURE | |
| One fault-close operation at 15.2 kV phase-to-ground, or 26.3 kV phase-to-phase; 10,000 amps rms symmetrical, 10 cycles, (0.17 seconds). |
|
| PRODUCTION TESTS | |
| 100% factory test for partial discharge and either AC HIDOT (40kV for 60 seconds) or impulse (BIL) 125kV, 1.2 x 50 microsecond wave. | |
Hubbell 15.2/26.3 kV underground connectors provide utilities with products having high reliability and low maintenance.
These connectors provide:
Hubbell separable connector bushing inserts and elbows are designed for use with single-conductor, concentric neutral power cable having extruded insulation shielding. With shield adapter products, the elbow can be used with cables having a metallic tape shield, wire shield, or lead sheath with tape or extruded insulation shielding.
All insulating and conducting rubber components are made of a special formulation of an EPDM elastomer using a peroxide curing process. The material and curing process provides superior elastomeric stress relaxation characteristics under high ambient temperatures and contributes to reliable, long-time operation in either above-ground or subsurface installations.
Elbow connector/bushing insert combinations are suitable for energized loadmake/loadbreak operations by a qualified lineman using a shotgun-type (Chance) hot stick.
All elbow/bushing insert combinations are designed for use with subsurface (submersible to 6 feet of water) or pad-mounted installations.
Hubbell 25 kV loadbreak products are designed for operation on and connection to 25 kV class, 125 kV BIL systems where the voltage ratings listed on this page are not exceeded.
|
|
All contents Copyright© 2001 -
Hubbell Incorporated. All rights reserved. Because Hubbell has a policy of
continuous product improvement, we reserve the right to change design specifications
without notice.