Home › Products › Cable Accessories › 200A Loadbreak › 25kV › Elbow
The Hubbell 25 kV Loadbreak Elbow Connector has been tested in accordance with the requirements of IEEE Standard 386, "Separable Insulated Connector Systems for Power Distribution Systems above 600 Volts." In accordance with provisions of the Standard, outlined in Paragraph 6.4,interchangeability testing has established complete interchangeability, as defined by Paragraph 6.4.1 of the Standard, with 25 kV Ioadbreak products presently manufactured by Elastimold® and limited interchangeability as defined by Paragraph 6.4.2 of the Standard with all other manufacturers. Test reports are available upon request.
The elbow, when mated a with loadbreak product meeting the requirements of IEEE Standard 386, is suitable for energized loadmake/loadbreak operations by a qualified lineman using a shotgun-type (Chance) hot stick.
Step 1: Determine the cable's insulation diameter either by measuring it (Do not measure over the insulation shield) or from the cable manufacturer's catalog. Select an elbow size from table "w" so that the insulation falls within the elbow's range.
Step 2: Select a connector code from table "x" that identifies the conductor size and stranding. Standard compression lug is a long, bi-metal connector.
Step 3: If the elbow is to be supplied with a capacitance test point ad a "T" to the end of the part number.
| Table W | ||
|---|---|---|
| Insulation Min/Max | ||
| Elbow Size | Inches | mm |
| 4 | 0.800" - 1.140" | 20,3 - 29,0 |
| 5 | 0.920" - 1.310" | 23,4 - 33,3 |
| Table X (AL or CU Conductor) |
||
|---|---|---|
| Connector Code | Stranded or Compressed | Compact or Solid |
| 1 | #6 | #4 |
| 2 | #3 - #4 | #2 or #3 |
| 3 | #2 | #1 |
| 4 | #1 | 1/0 |
| 5 | 1/0 | 2/0 |
| 6 | 2/0 | 3/0 |
| 7 | 3/0 | 4/0 |
| 8 | 4/0 | 250 |
Example, the part number for a 25kV loadbreak elbow with test point for 1/0 stranded, 260mil insulation with an OD over insulation of 0.955" would be: 225LE45T.
To specify this same elbow kit but with a ProbeLok® connector, add a "P" after the connector code, i.e. 225LE45PT.
To order a loadbreak elbow with an integral seal add a "J" after the "LE" in the part number. For an example: 225LEJ45T.
To order an elbow kit without a compression connector use part number: 225LE40T.
If the kit is to be supplied with a separate, cold-shrink seal kit for use on concentric neutral cables, add a "J" to the end of the part number. For example: 225LE45TJ.
If a cold-shrink, shield adapter is to be included in the kit, add an "S" to the end of the part number: 225LE45TS.
To order a replacement probe, use part number 225LBP.
To order a replacement compression connector, use part number 200LUGBx.
|
|