Home › Products › Connectors › Distribution › Bolted Connectors › Parallel Groove Clamps (Aluminum) › Arc Protection Ground
| Aluminum |
|---|
| APD |
| Material: | Castings - Aluminum alloy |
|---|---|
| Hardware-APD57-galvanized steel | |
| APD80-stainless steel | |
| Note: | A radial circuit requires an APD protector on the load side of the insulator only, while other circuit configurations, such as loops, require that they be installed on both sides of the line insulator. In both situations, they must be installed on all conductor phases and positioned outside the end of a tie wire. The covering must be stripped away over this distance including the area within the confines of a tie wire. Since an arc from one phase to the neutral will often expand to fault all three phases, the device must be installed on all three phases. |
| CATALOG NUMBER (WITH INHIBITOR) | MAX. O.D. OF CABLE JACKET-INCHES | CONDUCTOR RANGE O.D. IN INCHES | DIMENSION B-INCHES (MM) | APPROX. WT. 100 LBS. (KG) |
|---|---|---|---|---|
| (1) APD57XB (Fused circuits) | 0.906 | #1-4/0 STR. AAC #2-4/0 ACSR 0.31-0.57 | 1.06 (27) | 24 (11) |
| APD80XB | 1.200 | 2/0-556.5 Str. AAC 1/0-477 (18/1) ACSR 0.39-0.86 | 1.87 (48) | 66 (30) |
|
|