For sales and support visit:
hubbellpowersystems.com/contact/

Tube to Pad

EHV BOLTED TERMINALS
FOR TUBE TO FLAT PAD
TYPE HVSTF/EVSTF
ALUMINUM
HVSTF/EVSTF
  • Aluminum alloy, tube to flat, terminal connectors are designed for corona free service at 345 and 500 KV respectively. Tongue mounting hardware is not furnished as part of this catalog number. Hardware must be ordered separately, specifying thickness of the pad to be clamped. The hardware shield is furnished as part of this catalog number. Tongue holes have NEMA spacing. Contact sealant is recommended. Terminals with side formed contact may be ordered by adding “-SF” to catalog number (example: HVSTF-34-D-SF).
Material: Castings – 356-T6 aluminum alloy
Clamping Hardware – aluminum alloy
354 KV AND 500 KV LINE-TO-LINE APPLICATIONS
CATALOG NUMBER ALUMINUM CONDUCTOR SIZE TUBING IPS/EHIPS DIMENSIONS - INCHES (MM) APPROX. WT. EA. LBS.(KG)
A C F
345 KV APPLICATIONS
HVSTF-20-D 2 4 (101.60) 2 1/2 (63.50) 6 1/4 (158.75) 8.0 (3.63)
HVSTF-24-D 2 1/2 4 (101.60) 2 3/4 (69.85) 6 1/2 (165.10) 8.9 (4.04)
HVSTF-30-D 3 4 (101.60) 3 1/16 (77.79) 7 3/16 (182.56) 9.2 (4.17)
HVSTF-34-D 3 1/2 4 1/4 107.95) 3 5/16 (84.14) 7 7/8 (200.03) 9.8 (4.45)
HVSTF-40-D 4 4 1/4 (107.95) 3 9/16 (90.49) 8 3/8 (212.73) 10.7 (4.85)
500 KV APPLICATIONS
EVSTF-24-D 2 1/2 5 (127.00) 3 5/16 (84.14) 7 7/8 (200.03) 13.2 (5.99)
EVSTF-30-D 3 5 (127.00) 3 5/16 (84.14) 7 7/8 (200.03) 13.1 (5.94)
EVSTF-34-D 3 1/2 5 (127.00) 3 9/16 (90.49) 8 (203.20) 13.8 (6.27)
EVSTF-40-D 4 5 (127.00) 3 13/16 (96.84) 8 7/8 (203.20) 14.4 (6.53)
EVSTF-50-D 5 6 (152.40) 4 5/16 (109.54) 10 (254.00) 19.9 (9.03)
Hubbell Power Systems All contents Copyright© 2001 - Hubbell Incorporated. All rights reserved. Because Hubbell has a policy of continuous product improvement, we reserve the right to change design specifications without notice.
Terms of Use | Contact Us | Site Map