Home › Products › Connectors › Distribution › Standard Voltage › Reference Data › Aluminum Connectors
| If "A" BAR is | Cu | AL | AL | Galvanized Steel | Galvanized Steel |
| and "B" BAR is | Cu | Cu | AL | Cu | AL |
| Recommended Series of Hardware |
(1) Si-Br | (1) SS or GS | (1) AL | (1) Si-Br | (1) AL |
| (2) SS | (2) SS or GS | (2) SS or GS | (2) SS or GS | ||
| (3) GS |
(1) denotes preferred hardware usage.
Note: Contact sealant should be used between Aluminum to Aluminum and Aluminum to Copper connections.