Home › Products › Insulators › Distribution › Suspension (VLS)
| Catalog Numbers |
No. of Sheds |
"X" Length inches (mm) |
"D" Diameter Inches (mm) |
Net Wt. pounds (kg) |
Standard Package Qty. | 1SML pounds (kN) |
2RTL pounds (kN) |
3Proof pounds (kN) |
|
|---|---|---|---|---|---|---|---|---|---|
| Carton | Pallet | ||||||||
| 4050021301 | 4 | 11.5 (292) |
5.9 (150) |
4 (1.8) |
12 | 96 | 15,000 (70) |
7,500 (35) |
10,000 (44.5) |
| 4050029001** | 4 | 12.5 (318) |
5.9 (150) |
4 (1.8) |
12 | 96 | 15,000 (70) |
7,500 (35) |
10,000 (44.5) |
| 4050031301 | 6 | 17.25 (438) |
5.9 (150) |
4 (1.8) |
12 | 96 | 15,000 (70) |
7,500 (35) |
10,000 (44.5) |
| 4050041301 | 8 | 23 (584) |
5.9 (150) |
5 (2.3) |
12 | 96 | 15,000 (70) |
7,500 (35) |
10,000 (44.5) |
| 4050051301 | 10 | 28.75 (730) |
5.9 (150) |
6 (2.8) |
12 | 48 | 15,000 (70) |
7,500 (35) |
10,000 (44.5) |
| 4050061301 | 12 | 34.5 (876) |
5.9 (150) |
7 (3.2) |
12 | 48 | 15,000 (70) |
7,500 (35) |
10,000 (44.5) |
| Catalog Numbers |
Type | Leakage Distance Inches (mm) |
Dry Arc Distance Inches (mm) |
Flashover ANSI |
Critical Flashover ANSI |
RIV | Power Arc kA cycles |
Equivalent number of 10" x 5-3/4" Bells |
Volt* Class |
|||
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Dry-kV | Wet-kV | Pos-kV | Neg-kV | Test kV | Max. μV | |||||||
| 4050021301 | VLS-2 | 23 (584) |
11.75 (298) |
135 | 110 | 225 | 255 | 21 | <10 | 150 | 2 | 15/25 |
| 4050029001** | VLS-2 | 23 (584) |
11.75 (298) |
135 | 110 | 225 | 255 | 21 | <10 | 150 | 2** | 15/25 |
| 4050031301 | VLS-3 | 39 (991) |
18 (457) |
190 | 140 | 320 | 330 | 32 | <10 | 150 | 3 | 35/46 |
| 4050041301 | VLS-4 | 54 (1372) |
23.7 (602) |
255 | 190 | 420 | 435 | 48 | <10 | 150 | 4 | 46/69 |
| 4050051301 | VLS-5 | 69 (1753) |
29.5 (749) |
315 | 245 | 500 | 510 | 48 | <10 | 150 | 5 | 69 |
| 4050061301 | VLS-6 | 84 (2134) |
35.2 (894) |
370 | 305 | 610 | 580 | 48 | <10 | 150 | 6 | 69 |
| Suffix Code | Tower-end | Line-end |
|---|---|---|
| 1301 | ANSI 52-3 Socket | ANSI 52-3 Ball |
| 1400 | ANSI 52-6 Clevis | ANSI 52-6 Tongue |
| 2A07 | IEC 16 mm Socket | IEC 16 mm Ball |
VLS insulators are available with ANSI and IEC ball / socket end fittings and also with clevis/tongue end fittings. Please use the following 4-digit suffix codes after the 6-digit catalog number.
|
|
All contents Copyright© 2001 -
Hubbell Incorporated. All rights reserved. Because Hubbell has a policy of
continuous product improvement, we reserve the right to change design specifications
without notice.
Terms of Use | Contact Us | Site Map |