For sales and support visit:
hubbellpowersystems.com/contact/

Vertical Line Posts

Selection Guide Typical
Line Voltage, kV
Catalog # with
5" Bolt Circle &
Vert. Clamptop
"X"
Length
Inches
(mm)
No.
of
Sheds
Dry Arc
Distance
inches
(mm)
Leakage
Distance
inches
(mm)
(1) 60 Flashover ANSI (1) Critical Flashover ANSI (2)RCL
pounds
(kN)
Net
Weight
pounds
(kg)
69 115 138 161 Dry-kV Wet-kV Pos-kV Neg-kV
        5230051205 38.0 (965) 10 29 (737) 77 (1956) 295 250 445 540 2500 (11.1) 54 (24.5)
5230061205 43.2 (1097) 12 34 (864) 93 (2362) 345 295 530 620 2500 (11.1) 59 (26.8)
    5230071205 48.5 (1219) 14 39 (991) 108 (2743) 395 335 615 705 2500 (11.1) 64 (29.1)
5230081205 53.8 (1367) 16 45 (1143) 124 (3150) 445 380 695 785 2500 (11.1) 69 (31.4)
  5230091205 59.2 (1504) 18 50 (1270) 140 (3556) 495 420 780 870 2500 (11.1) 74 (33.6)
    5230101205 64.5 (1638) 20 55 (1397) 156 (3962) 545 465 865 950 2335 (10.4) 79 (35.9)