For sales and support visit:
hubbellpowersystems.com/contact/

Vertical Line Post

2.5" (63.5 mm) Rod Diameter

Selection Guilde:
Typical Line
Voltage, kV(1)
Catalog
Numbers(3)
Nominal
Polymer
Length
inches
Section
Length
inches
(mm)
Strike
Distance
inches
(mm)
Leakage
Distance
inches
(mm)
ANSI Values IEC Values SCL lbs.
(kN)
(2)
60-Hz
Dry
Flashover
(kV)
(2)
60-Hz
Wet
Flashover
(kV)
(2)
Critical
Impulse
Positive
(kV)
(2)
Critical
Impulse
Negative
(kV)
(2)
60-Hz
1-minute
Wet
Withstand
(kV)
(2)
Impulse
Positive
Withstand
(kV)
(2)
Impulse
Negative
Withstand
(kV)
69 110 132 161
        P250024S2050 24 35.0 (889) 25.0 (635) 63 (1600) 255 235 385 505 195 365 475 5000 (22.3)
P250026S2050 26 37.4 (950) 27.4 (696) 69 (1753) 280 255 425 540 215 400 510 5000 (22.3)
  P250031S2050 31 42.3 (1074) 32.2 (818) 82 (2083) 330 300 510 615 255 480 580 4200 (18.7)
  P250036S2050 36 47.1 (1196) 37.1 (942) 95 (2413) 380 345 580 690 290 550 655 3720 (16.6)
  P250043S2050 43 54.4 (1382) 44.3 (1125) 113 (2870) 455 405 700 800 340 665 760 3180 (14.2)
    P250048S2050 48 59.2 (1504) 49.2 (1250) 126 (3200) 515 450 770 880 380 730 835 2900 (12.9)
P250053S2050 53 64.1 (1628) 54.0 (1372) 139 (3531) 565 495 855 950 420 810 900 2660 (11.8)
  P250058S2050 58 68.9 (1750) 58.8 (1494) 151 (3835) 600 525 920 1025 445 870 970 2460 (10.9)
P250060S2050 60 71.3 (1811) 61.3 (1557) 158 (4013) 625 540 955 1065 455 905 1010 2370 (10.5)
Hubbell Power Systems All contents Copyright© 2001 - Hubbell Incorporated. All rights reserved. Because Hubbell has a policy of continuous product improvement, we reserve the right to change design specifications without notice.