Home › Products › Lineman Grade Tools › Jumpers / Load Pick-Up › Temporary Cutout Tools
To provide fuse protection during live-line maintenance, the temporary cutout tool simply clamps onto primary conductor with a Grip-All clampstick. Brass stud at lower end accepts clamp on temporary tap jumper. Insulated bushing and hot parts are from Chance Type C-Polymer cutouts: Upper contact with integral sleet shield and hooks for operation by loadbreak tool and lower trunnion of cast bronze. Fusetube must be fitted with fuselink rated no larger than 100 amps.
Available in ratings for 15kV and 27kV systems, tools come with or without a pivot-lever closing device.
| Catalog Number | REPLACES Cat. No. | System Class | Interrupt Capacity | Weight (lb/kg.) | Fuseholder Replacement |
|---|---|---|---|---|---|
| PSC6010341 | C6001895 | 15kV | 10,000 Amps | 7-1/4 / 3.3 |
T710112T |
| PSC6010342 | C6001896 | 27kV | 8,000 Amps | 10-1/2 / 4.8 |
T710211T |
| Catalog Number | REPLACES Cat. No. | System Class | Interrupt Capacity | Weight (lb/kg.) | Fuseholder Replacement |
|---|---|---|---|---|---|
| PSC6010343 | C6002862 | 15kV | 12,000 Amps | 8-1/4 / 3.7 |
T710133T |
| PSC6010344 | C6002863 | 27kV | 12,000 Amps | 11-1/2 / 5.2 |
T710233T |
| Main Line Range | Tap Stud | |
|---|---|---|
| Minimum | Maximum | |
| #6 Sol. Cu. (0.162") | 1033 kcmil ACSR (1.25") | 1/2" diameter |
| Catalog No. | REPLACES Cat. No. |
System Class | Weight |
|---|---|---|---|
| PSC6010345 | C6001944 | 15kV | 8-3/4 lb. / 3.97 kg. |
| PSC6010346 | C6001945 | 27kV | 12 lb. / 5.44 kg. |
|
|
All contents Copyright© 2001 -
Hubbell Incorporated. All rights reserved. Because Hubbell has a policy of
continuous product improvement, we reserve the right to change design specifications
without notice.