Home › Products › Switching › Distribution › Reclosers › Hardware Features
| Ratings and Specifications | |
|---|---|
| Rated Maximum Voltage | 27kV |
| Rated Continuous Current | 400A |
| Fault Make Capacity | 8kA |
| Fault Make Capacity Peak | 20.7kA |
| Fault Break Capacity | 8kA |
| Mechanical Operations | 30,000 |
| 3 Second Withstand Current | 8kA |
| Transformer Magnetizing Current | 14A |
| Cable Charging Current | 25A |
| Line Charging Current | 5A |
| Lightning Impulse Withstand | 125kV |
| 60Hz, 1-Minute Withstand Voltage | 60kV |
| Maximum Terminal Pad Load kg (pounds) | 14 (30) |
| Operating Temperature | -40°C to 60°C |
| Weight kg (pounds) | 25 (55) |
Programming recloser with serial port connections
In the closed position, the Versa-Tech® Recloser, operates automatically per the user-programmed settings.
The Manual Operating Handle allows manual operation of the recloser with a hotstick.
The Non-Reclosing Lever is shown above in its normal (or up) position. When this handle is rotated to the down position, the recloser will trip using TCC1 and lockout on any current above the minimum trip. The Non-Reclosing lever does not interfere with the Manual Operating Handle.
The Lockout Beacon is a unique feature to aid the utility lineman in identifying a locked out recloser. This highbrightness, sunlight-visible amber LED will flash once every 3 seconds when the recloser has sequenced to lockout. The beacon will continue to flash every 3 seconds until the lineman closes the recloser or 4 hours have passed. After 4 hours, the flashing beacon will automatically shut off. Powered by the recloser's lithium batteries, the beacon's duty cycle was set to have a negligible effect on battery life.
The Operations Counter is an electromechanical counter which records the number of open operations, both manual and automatic, initiated by the control.
The Versa-Tech® Recloser has been designed for a minimum mechanical life of 2500 operations. No routine maintenance is required.
Battery power is used for these functions only: To close the recloser after installation or lockout, the radio if load current is less than 5 amps, and the flashing lockout beacon. The batteries are made of a very stable lithium chemistry, which is designed with a low self discharge that they can function correctly for up to 10 years. Hubbell Power Systems recommends that users replace the batteries on an 8 year cycle.
The battery bayonet was designed to be replaced using a hot stick while the recloser is in service. The battery bayonet utilizes a twist lock design. It is easily removed by pushing in slightly and turning.
|
|